{"trade":"ev-charging","month":"2019-10","monthStart":"2019-10-01","monthEnd":"2019-10-31","fetchedAt":"2026-08-02T09:55:40.573Z","source":{"dataset":"ydr8-5enu","api":"https://data.cityofchicago.org/resource/ydr8-5enu.json","page":"https://data.cityofchicago.org/Buildings/Building-Permits/ydr8-5enu"},"ok":true,"error":null,"total":4,"totalReportedCost":11975,"costedCount":4,"largestReportedCost":6500,"truncated":false,"permits":[{"permit":"B100842115","permitType":"PERMIT – EXPRESS PERMIT PROGRAM","issueDate":"2019-10-29","address":"1660 N OAKLEY AVE","workDescription":"**ELECTRICAL ONLY PERMIT**400 AMP SERVICE UPGRADE   $5,000.00 1. REMOVE EXISTING 200 AMP METER FITTING AND RISER. 2. FURNISH AND INSTALL (1) NEW 400 AMP OVERHEAD METER FITTING. 3. FURNISH AND INSTALL (3) #500 MCM CU SERVICE RISER CONDUCTORS. 4. FURNISH AND INSTALL (1) NEW CUTLER HAMMER BRAND 200 AMP, MAIN BREAKER, 40 CIRCUIT PANEL. 5. FURNISH AND INSTALL (3) #3/0 THHN CU SERVICE ENTRANCE CONDUCTORS FROM THE METER FITTING TO THE NEW PANEL AND TO RE-FEED THE EXISTING PANEL. 6. EXISTING PANEL TO REMAIN AND BE RE-FEED. 7. FURNISH AND INSTALL (2) NEW GROUND RODS. 8. FURNISH AND INSTALL NEW UPDATED WATER GROUND AS REQUIRED BY CODE. 9. COORDINATE ALL PAPERWORK AND NEEDED SITE INSPECTIONS WITH THE CITY OF CHICAGO AND COM ED. 10. PROPOSAL DOES NOT INCLUDE ANY PERMIT FEES OR FEES INCURRED BY COM ED.  TESLA EV CHARGER NEMA 14-50R $1,200.00 1. FURNISH AND INSTALL (1) 50 AMP, 240 VOLT, 4 WIRE DEDICATED CIRCUIT. 2. PROPOSAL INCLUDES RUNNING (1) 3/4\" RIGID EMT CONDUIT INSTALLED FROM THE NEW 200 AMP P","reportedCost":6500,"cityRecordUrl":"https://data.cityofchicago.org/resource/ydr8-5enu.json?permit_=B100842115"},{"permit":"B100846680","permitType":"PERMIT – EXPRESS PERMIT PROGRAM","issueDate":"2019-10-17","address":"1225 W MORSE AVE","workDescription":"TESLA EV CHARGER NEMA 14-50R $1,800.00 1. FURNISH AND INSTALL (1) 50 AMP, 240 VOLT, 4 WIRE DEDICATED CIRCUIT. 2. PROPOSAL INCLUDES RUNNING (1) 3/4\" RIGID EMT CONDUIT INSTALLED FROM ONE 200 AMP PUBLIC PANEL TO THE GARAGE PARKING SPOT. 3. CIRCUITRY WILL CONSIST OF (3) #6AWG THHN COPPER CONDUCTORS AND (1) #10 AWG THHN GROUNDING CONDUCTOR. 4. FURNISH AND INSTALL (1) NEMA 14-50R. RECEPTACLE WILL BE LOCATED BY YOUR PARKING SPACE. 5. RECEPTACLE WILL DELIVER 32 AMPS AND PROVIDE 30 MILES PER HOUR OF CHARGE. (MODEL 3) 6. FURNISH AND INSTALL (1) 50 AMP, 2 POLE BREAKER. 7. PROVIDE (1) LOAD CALCULATION FOR THE HOUSE PANEL INCLUDING THE NEW TESLA CHARGER.  EV CIRCUIT SUB METER $565.00 1. FURNISH AND INSTALL (1) LEVITON BRAND SUB METER TO MONITOR ELECTRICITY USAGE OF THE EV CHARGER.","reportedCost":2365,"cityRecordUrl":"https://data.cityofchicago.org/resource/ydr8-5enu.json?permit_=B100846680"},{"permit":"B100845243","permitType":"PERMIT – EXPRESS PERMIT PROGRAM","issueDate":"2019-10-09","address":"1201 W ADAMS ST","workDescription":"TESLA EV CHARGER NEMA 14-50R $1,345.00 1. FURNISH AND INSTALL (1) 50 AMP, 240 VOLT, 4 WIRE DEDICATED CIRCUIT. 2. PROPOSAL INCLUDES RUNNING (1) 3/4\" RIGID EMT CONDUIT INSTALLED FROM EXISTING 200 AMP PUBLIC PANEL TO THE GARAGE PARKING SPOT. 3. CONDUIT WILL BE SURFACE MOUNTED IN THE GARAGE. 4. CIRCUITRY WILL CONSIST OF (3) #6AWG THHN COPPER CONDUCTORS AND (1) #10 AWG THHN GROUNDING CONDUCTOR. 5. FURNISH AND INSTALL (1) NEMA 14-50R. 6. RECEPTACLE WILL DELIVER 32 AMPS AND PROVIDE 30 MILES PER HOUR OF CHARGE. (MODEL 3) 7. FURNISH AND INSTALL (1) 50 AMP, 2 POLE BREAKER.   EV CIRCUIT SUB METER $565.00 1. FURNISH AND INSTALL (1) LEVITON BRAND SUB METER TO MONITOR ELECTRICITY USAGE OF THE EV CHARGER.","reportedCost":1910,"cityRecordUrl":"https://data.cityofchicago.org/resource/ydr8-5enu.json?permit_=B100845243"},{"permit":"B100843555","permitType":"PERMIT – EXPRESS PERMIT PROGRAM","issueDate":"2019-10-01","address":"2123 W POTOMAC AVE","workDescription":"TESLA EV CHARGER NEMA 14-50R (#UNDERGROUND)  $1,200.00 1. FURNISH AND INSTALL (1) 50 AMP, 240 VOLT, 4 WIRE DEDICATED CIRCUIT. 2. PROPOSAL INCLUDES RUNNING (1) 3/4\" RIGID EMT CONDUIT INSTALLED FROM THE 200 AMP PANEL TO THE GARAGE. CONDUIT WILL BE SURFACE MOUNTED IN THE GARAGE. 3. CIRCUITRY WILL CONSIST OF (3) #6AWG THHN COPPER CONDUCTORS AND (1) #10 AWG THHN GROUNDING CONDUCTOR. 4. FURNISH AND INSTALL (1) NEMA 14-50R. RECEPTACLE WILL BE LOCATED ON THE BACK NORTH WEST CORNER WALL OF THE GARAGE. RECEPTACLE WILL DELIVER 32 AMPS AND PROVIDE 30 MILES PER HOUR OF CHARGE. (MODEL 3) 5. FURNISH AND INSTALL (1) 50 AMP, 2 POLE BREAKER. 6. PROVIDE (1) LOAD CALCULATION FOR THE HOUSE INCLUDING THE NEW TESLA CHARGER. 7. PROPOSAL INCLUDES TRENCHING AND BACKFILLING. LANDSCAPE RESTORATION IS NOT INCLUDED. PROPOSAL ALSO INCLUDES COORDINATING DIG WITH J.U.L.I.E. TO LOCATE ANY UNDERGROUND UTILITIES.","reportedCost":1200,"cityRecordUrl":"https://data.cityofchicago.org/resource/ydr8-5enu.json?permit_=B100843555"}],"recordLimit":100}